02 322 1678-87 Burner 02 322 9365-66 info@boonyium.com @boonyium
TH | EN
SIEMENSburner-controllers

Siemens Burner Controllers LGA

Siemens Burner Controllers LGA Series are gas burner control units designed for the startup and flame supervision of small to medium-capacity gas burners operating intermittently. They provide ignition sequence control, ionization flame monitoring, gas valve control, and safety lockout protection. Selected models support auxiliary fan and air pressure switch connections, making the series suitable for maintaining and replacing compatible burner controls in existing gas-fired heating systems.

Product Details

Siemens Burner Controllers LGA

Siemens Burner Controllers LGA Series

Siemens Burner Controllers LGA Series are gas burner control units designed for the startup and flame supervision of small to medium-capacity atmospheric gas burners operating in intermittent mode.

The controllers manage the burner ignition sequence, gas valve operation, and flame supervision using an ionization probe. They help ensure that the combustion system follows the required safety sequence during startup and operation.

Key Features

  • Automatic startup and ignition sequence control for gas burners
  • Flame supervision using an ionization probe
  • Two gas valve control outputs (BV1 and BV2)
  • Safety lockout protection in the event of ignition failure or abnormal flame signals
  • Auxiliary fan and air pressure switch connections on LGA52 and LGA63 models
  • Integrated lockout warning lamp and manual reset button
  • Plug-in design for convenient installation and replacement
  • Can replace selected LFI7 and LFI5 predecessor models using suitable adapters, subject to compatibility verification

Operating Principle

When a startup command is received, the LGA burner control initiates the ignition sequence according to the selected model.

The controller operates the ignition transformer and gas valves while supervising flame establishment through the ionization probe.

When a valid flame signal is detected, the controller permits the burner to proceed to its operating stage.

If a flame is not established within the specified ignition safety time, the controller initiates safety lockout to prevent continued fuel release.

Available Series

  • LGA41 Series: Designed for gas burner control without auxiliary fan connections.
  • LGA52 Series: Supports auxiliary fan and air pressure switch connections.
  • LGA63 Series: Supports auxiliary fan operation, air pressure monitoring, and undervoltage detection.

Typical Applications

  • Small and medium-capacity gas burners
  • Gas-fired industrial heating equipment
  • Intermittently operated gas combustion systems
  • Maintenance of existing burner control systems
  • Replacement of compatible legacy gas burner controllers
Important Notice: Siemens states that the LGA Series should not be used for new designs. LME Series burner controls are recommended for new applications. Verify the model, electrical ratings, wiring configuration, and operating sequence before replacing an existing controller.
Siemens Burner Controllers LGA

Technical Specifications

Siemens LGA Series Technical Specifications

Specification Technical Data
Brand Siemens
Product Series LGA Series
Product Type Gas Burner Controls
Application Small to medium-capacity gas burners, intermittent operation
Supply Voltage AC 220–240 V or AC 100–110 V, depending on model
LGA63: AC 230 V ±10%
Mains Frequency 50–60 Hz ±6%
Power Consumption 3 VA
Input Current at Terminal 1 Max. 5 A
Flame Detection Ionization Probe
Minimum Detector Current 5 µA
Maximum Possible Detector Current 100 µA
Detector Cable Length Max. 20 m (separate cable)
Minimum Insulation Resistance 50 MΩ
Gas Valve Control Outputs 2 (BV1 and BV2)
Degree of Protection IP40 (when integrated)
Operating Temperature 0 to +60°C
LGA41.173A27 / LGA52.171B27: -20 to +60°C
Relative Humidity Below 95% RH
Weight Approx. 180 g
Mounting Type Plug-in
Compatible Plug-in Base AGK11 Series (accessory)

Model Variants and Ignition Safety Time

Model Supply Voltage Safety Time (TSA)
LGA41.153A27 AC 220–240 V 5 seconds
LGA41.173A27 AC 220–240 V 10 seconds
LGA52.150B27 AC 220–240 V 5 seconds
LGA52.150B17 AC 100–110 V 5 seconds
LGA52.171B27 AC 220–240 V 4.5–7.5 seconds
LGA63.191A27 AC 230 V 10 seconds

Note: The timing values above apply at AC 220 V or AC 110 V, depending on the model. For operation at AC 240 V, Siemens specifies a timing multiplier of 0.7. Refer to the manufacturer's data sheet before installation or replacement.

Dimensions

Documents & Downloads

GAS-BURNER-CONTROL-LGA._2013-boonyiumPDF
Download

Frequently Asked Questions

For product questions, please contact our engineering team.

Need expert assistance?

Our engineers can help choose suitable equipment.

Contact us

Request a Quotation / Product Inquiry

Send your product inquiry and our team will contact you.