02 322 1678-87 Burner 02 322 9365-66 info@boonyium.com @boonyium
TH | EN
SIEMENSburner-controllers

Siemens Burner Controls LMV6

Siemens Burner Controls LMV6 Series is a microprocessor-based Burner Management System designed for medium- to large-capacity forced draft gas burners. It integrates burner sequencing, flame supervision, electronic fuel-air ratio control for up to three actuators, gas valve proving, and flue gas recirculation (FGR). With CAN bus communication and compatibility with the AZL66 operating unit, the LMV6 supports reliable burner operation, diagnostics, and combustion management in industrial boiler and heating applications.

Product Details

Siemens Burner Controls LMV6

Siemens Burner Controls LMV6 Series

Siemens LMV6 Series is a microprocessor-based Burner Management System designed for controlling and monitoring medium- to large-capacity forced draft gas burners. It provides integrated burner sequencing, ignition control, flame supervision, and combustion management functions.

The LMV6 combines electronic fuel-air ratio control, gas valve proving, and flue gas recirculation (FGR) within a coordinated burner management platform. The system supports up to three actuators and provides CAN bus communication for compatible system components.

Key Features of Siemens LMV6

  • Integrated burner control and ignition sequencing
  • Electronic fuel-air ratio control
  • Supports up to three actuators
  • Integrated gas valve proving system
  • Flue gas recirculation (FGR) functionality
  • Flame supervision using an ionization probe or compatible UV flame detectors
  • CAN bus communication for compatible system components
  • Fault history and operating status diagnostics
  • Parameterizable program times and functions
  • Separate restart counter for each fuel

Flame Supervision

The LMV6 supports flame supervision using an ionization probe for continuous operation. For intermittent operation, compatible flame detectors include QRA2, QRA2M, QRA4, and QRA10 UV flame detectors, as well as ionization probes.

Control and Communication

The system communicates with compatible components through its integrated CAN bus interface. The AZL66 display and operating unit enables menu-driven parameterization, operating status monitoring, and fault diagnostics. Password-protected access levels help prevent unauthorized parameter changes.

Typical Applications

  • Medium- to large-capacity forced draft gas burners
  • Industrial boiler systems
  • Industrial heating equipment
  • Combustion systems requiring electronic fuel-air ratio control
  • Burner installations requiring advanced monitoring and diagnostics
Important Note: Installation, commissioning, and parameterization of the LMV6 must be performed by qualified personnel in accordance with Siemens technical documentation and applicable safety requirements.
Siemens Burner Controls LMV6

Technical Specifications

Siemens LMV6 Series Technical Specifications

Brand Siemens
Series LMV6 Series
Reference Model LMV60.110A2
Article Number S55402-C403-A100
Product Type Burner Management System
Application Medium- to Large-Capacity Forced Draft Gas Burners
Control Technology Microprocessor-based
Mains Voltage 230 V AC (-15% / +10%)
Mains Frequency 50 Hz ±6%
Power Consumption Less than 35 W (Typical)
External Primary Fuse Max. 6.3 A, Slow-blow
Maximum Actuators 3
Ratio Control Electronic Fuel-Air Ratio Control
Gas Valve Proving Integrated
Flue Gas Recirculation Supported (FGR)
Communication Interface CAN Bus
Display and Operating Unit AZL66
Compatible Actuators SQM4 Series
Flame Detectors Ionization Probe, QRA2, QRA2M, QRA4, QRA10
Operating Modes Continuous and Intermittent Operation
Degree of Protection IP00
Operating Temperature -20 to +60°C
Relative Humidity Less than 95% RH
Maximum Installation Altitude 2,000 m Above Sea Level
Weight Approx. 870 g
Mounting DIN Rail TH 35-7.5, EN 60715
Applicable Standards DIN EN 298, DIN EN 1643, DIN EN 13611, EN 60730-2-5
Designed Lifetime 250,000 Burner Startup Cycles or Approximately 10 Years Under Specified Conditions

Source: Siemens Technical Data Sheet CC1N7560en, March 4, 2020. Specifications refer to LMV60.110A2 and are subject to manufacturer revisions.

Dimensions

Documents & Downloads

SIEMENS-BURNER-MANAGEMENT-SYSTEM-LMV6-boonyiumPDF